

— News —
Service Hotline +86-15618746768 Email:services@qinsun-lab.com
Landline:+8615618746768
Telephone:+86-15618746768
Address:Unit 3A, 20/F,Far East Consortium Building,121 Des Voeux Road Central, Hong Kong
Product News
time:2026-03-04 click:
The Needle Flame Tester is a flammability testing device used to evaluate the ignition hazard of solid materials—such as electrical and electronic equipment, insulating materials, and engineering plastics—when exposed to a small flame simulating internal fault conditions.
Its primary purposes include:
Simulating small flames generated by internal product faults (such as leakage currents or poor electrical contacts);
Assessing the flame-retardant performance and ignition risk of materials or components;
Providing a suitable method for products that cannot be effectively evaluated by the Glow Wire Test or horizontal/vertical burning tests (UL 94).

The core working principle is based on applying a standardized small flame to the specimen and observing its combustion behavior.
Flame Generation
Butane (or propane) gas with a purity of ≥95% is discharged through a stainless-steel needle burner with an internal diameter of 0.5 mm ± 0.1 mm and ignited to produce a stable, controllable needle-shaped flame.
Flame Parameter Control
Flame height: 12 mm ± 1 mm
Flame tip temperature: 800°C ± 10°C
Gas pressure: 20 kPa ± 2 kPa
These parameters ensure flame stability and repeatability.
Flame Application
The flame is applied to the specimen at a 45° angle for a specified duration (typically 10 s or 30 s, depending on the standard).
Result Evaluation
Material flame-retardant performance is assessed by observing and recording:
Whether ignition occurs
Afterflame time
Burning length or extinction behavior
This test is conducted in accordance with IEC 60695-11-5 and other relevant standards, and is widely used in electronics, automotive, and construction industries to evaluate fire hazards under simulated internal fault conditions.
The Needle Flame Test is a critical method for evaluating flame resistance under small-flame ignition risk. Its advantages include:
Accurately simulating micro-flames generated by internal faults in electrical and electronic equipment;
Assessing ignition characteristics of high-risk small components such as insulating materials and connectors;
Quantifying ignition resistance, flame spread, and self-extinguishing performance;
Ensuring compliance with IEC 60695 and other international safety standards.
This enables manufacturers to identify and improve flammable weaknesses during product design, enhance safety and compliance, and reduce fire risks and liability.
The procedure is primarily based on IEC 60695-11-5 and GB/T 5169.5-2008.
Equipment Calibration
Annual calibration by a qualified institution;
Daily inspection after startup;
Temperature response from 100°C to 700°C must be ≤23.5 ± 1 s;
Flame height must meet 12 ± 1 mm.
Gas Supply Connection
Use butane gas with purity ≥95%;
Check airtightness;
Ensure stable gas pressure.
Environmental Requirements
Well-ventilated test room without strong airflow interference;
A 10 mm white pine board covered with tissue paper is placed 200 ± 5 mm below the specimen.
Specimen Installation
Mount the specimen vertically in the holder;
Ensure unobstructed test surface;
Adjust the burner position so the flame tip is 8 mm from the bottom or 5 mm from the side of the specimen.
Flame Calibration and Adjustment
Ignite burner (purge air before first use);
Adjust gas flow to produce a stable blue conical flame (12 ± 1 mm);
Set burner angle to 45° during testing (vertical during calibration).
Parameter Setting
Typical flame application time: 30 s (adjustable 0–999.9 s);
Select underlay status (with or without) as required.
Start Test
Move burner to contact specimen and start timing;
Observe ignition behavior, afterflame duration, and whether molten droplets ignite the tissue paper.
Completion and Recording
Record afterflame time (tb), defined as the time from flame removal until complete extinction;
If tb ≤ 30 s and the underlay does not ignite or char, the specimen is typically considered compliant.
Shutdown and Cleaning
Close gas valve and power supply;
Activate exhaust system;
Clean residue after cooling.
Evaluation Criteria
Pass Criteria (unless otherwise specified):
Afterflame time ≤ 30 s;
Underlay does not ignite or char;
No sustained burning or flame spread beyond test area.
Classification
Some systems support classification such as V-0. V-1. V-2. or HB (according to UL 94).
Safety Precautions
Do not open the chamber door during testing;
In case of gas leakage, press emergency stop and close main valve;
Use CO₂ or dry powder extinguishers (never water-based);
Test alarm system sensitivity weekly.
Proper maintenance ensures stable operation, accurate results, and laboratory safety compliance.
Cleaning Before and After Testing
Clean combustion chamber residues after each test (power and gas off);
Remove specimens only after cooling to room temperature.
Burner Maintenance
After cooling, remove nozzle and clean with a fine wire to remove carbon deposits;
For stubborn contamination, soak in neutral detergent;
Ensure ignition electrode spacing is 5–10 mm.
Gas Line Inspection
Check hose connections and aging;
Adjust flame control valve to minimum before ignition.
Flame Height: 12 ± 1 mm
Burner Angle: 45° ± 2°
Timing System Error: ≤ ±0.5 s (at 10 s, 30 s, 60 s, 120 s checkpoints)
Temperature Response: 100°C to 700°C within 23.5 ± 1 s
Temperature Indication Error: Calibrated with platinum resistance thermometer and dry-block furnace at 100°C and 700°C.
Personal Protection
Operators must wear flame-retardant clothing, heat-resistant gloves, goggles, and face shields. Tie back long hair and remove flammable items.
Environmental Safety
Establish a 1-meter safety perimeter;
Use fire-resistant laboratory surfaces;
Ensure proper ventilation to remove toxic gases such as CO and HCN.
Emergency Measures
In case of gas leakage, close gas source immediately and ventilate;
If fire spreads, use nearby extinguisher and cut off power and fuel;
For burns, rinse with cold water and seek medical care if necessary.
Operational Discipline
Confirm no gas leakage before ignition;
After testing, close gas supply first, burn off residual gas, then cut power;
Ensure equipment temperature drops below 50°C before next test.
The Needle Flame Tester is a widely used flammability evaluation instrument that simulates real fire conditions to assess material combustion performance.Correct operating procedures and strict compliance with standards ensure the accuracy and repeatability of test results. At the same time, comprehensive safety precautions are essential to prevent fire hazards and other accidents during testing.
Related